Three-phase four-wire shut active power filter with coupled inductors
CHEN Xiao 1,2, Chen Heng-Lin1, CHEN Guo-zhu1
1. College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China; 2. School of Automation and Electrical Engineering, Zhejiang University of Science and Technology, Hangzhou 310023, China
A configuration of three-phase four-wire shunt active power filter(SAPF) which included the coupled inductors and the neutral wire filter inductors was proposed in this paper to resolve the problems of increasing equipment measurement and cost due to using three uncoupled inductors in the output filter of the traditional SAPF. The positive-sequence, negative-sequence, zero-sequence equivalent models of the three-phase three-column coupled inductor which included assistant winding were deduced in detail. The decoupling equivalent circuits of the system were obtained. And the controllers of system were designed. Compared with the traditional three-phase four-wire SAPF, simulation results under mostly working conditions show not only better steady-state compensation accuracy and stronger ability of restraining switching ripple of neutral wire but also better dynamic performances for the proposed configuration. Experimental results verify the feasibility of the proposed configuration.
CHEN Xiao, Chen Heng-Lin, CHEN Guo-zhu. Three-phase four-wire shut active power filter with coupled inductors. JOURNAL OF ZHEJIANG UNIVERSITY (ENGINEERING SCIENCE), 2015, 49(8): 1529-1536.
[1] AKAGI H. New trends in active filters for power conditioning [J]. IEEE Transactions on Industry Applications, 1996,32(6): 1312-1322.
[2] ORTS S, GIMENO-SALES F J, ABELLAN A, et al. Achieving maximum efficiency in three-phase systems with a shunt active power compensator based on IEEE Std. 1459 [J]. IEEE Transactions on Power Delivery, 2008, 23(2): 812-822.
[3] LISERRE M, BLAABJERG F. Design and control of an LCL-filter-based three-phase active rectifier [J]. IEEE Transactions on Industry Applications, 2005, 41(5): 1281-1291.
[4] 武健,徐殿国,何娜.并联有源滤波器输出LCL滤波器研究[J].电力自动化设备, 2007(1): 17-20.
WU Jian, XU Dian-guo, HE Na. Research on LCL filter applied to shunt active power filter [J]. Electric Power Automation Equipment, 2007(1): 17-20.
[5] 陈良亮,肖岚,胡文斌,等.一种基于耦合电感的逆变器并联系统环流抑制方法[J].南京航空航天学报, 2004, 36(2): 205-209.
CHEN Liang-liang, XIAO Lan, HU Wen-bin, et al. Circulating-current restraining method Based on coupled inductors in parallel inverter system [J]. Journal of Nanjing University of Aeronautics & Astronautics, 2004, 36(2): 205-209.
[6] SHIN D, LEE J P, LEE K J, et al. 1.5MVA grid-connected interleaved inverters using coupled inductors for wind power generation system [C]∥ Energy Conversion Congress and Exposition (ECCE). Denver CO: IEEE, 2013: 4689-4696.
[7] HE Chao, XIE Chuan, CHEN Guo-zhu. Study on Shunt Active Power Filters with Coupled Inductors [C]∥ Proceedings of the 2011 IEEE International Symposium on Industrial Electronics (ISIE2011). Gdansk: IEEE, 2011: 438-443.
[8] DAI Ning-yi, WONG Man-chung, HAN Yin-duo.Application of a three-level NPC inverter as a three-phase four-wire power quality compensator by generalized 3DSVM [J]. IEEE Trans. on Power Electronics, 2006, 21(2): 51-58.
[9] 唐健,邹旭东,佘煦,等.三相四线制三电平三桥臂有源滤波器中点平衡控制策略[J].中国电机工程学报,2009, 29(24): 40-48.
TANG Jian, ZOU Xu-dong, SHE Xu, et al. A Research on neutral-point potential balancing control strategy for three-phase- four-wire tri-level three-leg APFs [J]. Proceedings of the CSEE, 2009, 29(24): 40-48.
[10] 顾伟峰.一种应用于三相四线制并网变流器的三相电抗器:中国.201210467602.9[P]. 2013-02-20.
GU Wei-Feng. The three-phase reactor applied to three-phase four-wire grid-connected inverter. China. 201210467602.9 [P]. 2013-02-20.
[11] 陈国柱,王智强,谢川,等.高补偿精度并联型有源电力滤波器的控制策略[J].高电压技术, 2010(8): 2060-2067.
CHEN Guo-zhu, WANG Zhi-qiang, XIE Chuan, et al. Control strategy for shunt active power filters with high compensation precision [J]. High Voltage Engineering, 2010(8): 2060-2067.
[12] 王立峰,郑建勇,梅军,等.有源滤波装置直流侧电压控制瞬时能量平衡建模[J].电工技术学报, 2012(2): 229-234.
WANG Li-feng, ZHENG Jian-yong, MEI Jun, et al. Instantaneous energy equilibrium modeling of DC side voltage control for active power filter device [J]. Transactions of China Electrotechnical Society, 2012(2): 229-234.