制冷剂快速泄漏过程中分体空调系统运行特性的实验研究 |
张绍志1,2( ),方家浩1,2,梁璐瑶1,2,李泽田1,2,陈光明1,2,*( ) |
1. 浙江省制冷与低温技术重点实验室,浙江 杭州 310027 2. 浙江大学制冷与低温研究所,浙江 杭州 310027 |
|
Experimental study on operating characteristics of split air conditioning system during rapid leakage of refrigerant |
Shao-zhi ZHANG1,2( ),Jia-hao FANG1,2,Lu-yao LIANG1,2,Ze-tian LI1,2,Guang-ming CHEN1,2,*( ) |
1. Key Laboratory of Refrigeration and Cryogenic Technology of Zhejiang Province, Hangzhou 310027, China 2. Institute of Refrigeration and Cryogenic, Zhejiang University, Hangzhou 310027, China |
引用本文:
张绍志,方家浩,梁璐瑶,李泽田,陈光明. 制冷剂快速泄漏过程中分体空调系统运行特性的实验研究[J]. 浙江大学学报(工学版), 2023, 57(10): 2086-2093.
Shao-zhi ZHANG,Jia-hao FANG,Lu-yao LIANG,Ze-tian LI,Guang-ming CHEN. Experimental study on operating characteristics of split air conditioning system during rapid leakage of refrigerant. Journal of ZheJiang University (Engineering Science), 2023, 57(10): 2086-2093.
链接本文:
https://www.zjujournals.com/eng/CN/10.3785/j.issn.1008-973X.2023.10.017
或
https://www.zjujournals.com/eng/CN/Y2023/V57/I10/2086
|
1 |
FRANCIS C, MAIDMENT G, DAVIES G An investigation of refrigerant leakage in commercial refrigeration[J]. International Journal of Refrigeration, 2017, 74: 12- 21
doi: 10.1016/j.ijrefrig.2016.10.009
|
2 |
ROGERS A P, GUO F, RASMUSSEN B P A review of fault detection and diagnosis methods for residential air conditioning systems[J]. Building and Environment, 2019, 161: 106236
doi: 10.1016/j.buildenv.2019.106236
|
3 |
ROSSI T M, BRAUN J E A statistical, rule-based fault detection and diagnostic method for vapor compression air conditioners[J]. HVAC and R Research, 1997, 3 (1): 19- 37
doi: 10.1080/10789669.1997.10391359
|
4 |
BEHFAR A, YUILL D, YU Y Automated fault detection and diagnosis for supermarkets–method selection, replication, and applicability[J]. Energy and Buildings, 2019, 198: 520- 527
doi: 10.1016/j.enbuild.2019.06.011
|
5 |
SUN K, LI G, CHEN H, et al A novel efficient SVM-based fault diagnosis method for multi-split air conditioning system ’s refrigerant charge fault amount[J]. Applied Thermal Engineering, 2016, 108: 989- 998
doi: 10.1016/j.applthermaleng.2016.07.109
|
6 |
COTRUFO N, ZMEUREANU R PCA-based method of soft fault detection and identification for the ongoing commissioning of chillers[J]. Energy and Buildings, 2016, 130: 443- 452
doi: 10.1016/j.enbuild.2016.08.083
|
7 |
LIU J, SHI D, LI G, et al Data-driven and association rule mining-based fault diagnosis and action mechanism analysis for building chillers[J]. Energy and Buildings, 2020, 216: 109957
doi: 10.1016/j.enbuild.2020.109957
|
8 |
SHI S, LI G, CHEN H, et al An efficient VRF system fault diagnosis strategy for refrigerant charge amount based on PCA and dual neural network model[J]. Applied Thermal Engineering, 2018, 129: 1252- 1262
doi: 10.1016/j.applthermaleng.2017.09.117
|
9 |
EOM Y H, YOO J W, HONG S B, et al Refrigerant charge fault detection method of air source heat pump system using convolutional neural network for energy saving[J]. Energy, 2019, 187: 115877
doi: 10.1016/j.energy.2019.115877
|
10 |
VJACHESLAV N, ROZHENTSEV A, WANG C Rationally based model for evaluating the optimal refrigerant mass charge in refrigerating machines[J]. Energy Conversion and Management, 2001, 42 (18): 2083- 2095
doi: 10.1016/S0196-8904(00)00164-3
|
11 |
CHEN X, LI Z, ZHAO Y, et al Modelling of refrigerant distribution in an oil-free refrigeration system using R134a[J]. Energies, 2019, 12 (24): 4792
doi: 10.3390/en12244792
|
12 |
黄小清. 数据中心空调系统制冷剂泄漏故障的检测与诊断研究[D]. 上海: 上海交通大学, 2018: 23-28. HUANG Xiao-qing. Research on detection and diagnosis of refrigerant leakage fault in air conditioning system of data center [D]. Shanghai: Shanghai Jiao Tong University, 2018: 23-28.
|
13 |
ZHAO X, YANG M, LI H Field implementation and evaluation of a decoupling-based fault detection and diagnostic method for chillers[J]. Energy and Buildings, 2014, 72: 419- 430
doi: 10.1016/j.enbuild.2014.01.003
|
14 |
张网, 杨昭, 王婕, 等 分体式空调器使用R290作为制冷剂的泄漏研究[J]. 制冷学报, 2013, 34 (6): 42- 47 ZHANG Wang, YANG Zhao, WANG Jie, et al Research on leakage of split air conditioner using R290 as refrigerant[J]. Journal of Refrigeration, 2013, 34 (6): 42- 47
|
15 |
唐唯尔. R290在房间空调器和热泵系统中应用的安全性研究[D]. 武汉: 华中科技大学, 2018: 34-40. TANG Wei-er. Study on the safety of R290 applied in room air conditioner and heat pump system [D]. Wuhan: Huazhong University of Science and Technology, 2018: 34-40.
|
16 |
TANG W, HE G, ZHOU S, et al The experimental study of R290 mass distribution and indoor leakage of 2 HP and 3 HP split type household air conditioner[J]. International Journal of Refrigeration, 2019, 100: 246- 254
doi: 10.1016/j.ijrefrig.2019.02.001
|
17 |
HU X, ZHANG Z, YAO Y, et al Experimental analysis on refrigerant charge optimization for cold storage unit[J]. Procedia Engineering, 2017, 205: 1108- 1114
doi: 10.1016/j.proeng.2017.10.179
|
18 |
LI Z, JIANG H, CHEN X, et al Optimal refrigerant charge and energy efficiency of an oil-free refrigeration system using R134a[J]. Applied Thermal Engineering, 2020, 164: 114473
doi: 10.1016/j.applthermaleng.2019.114473
|
19 |
PELELLA F, VISCITO L, MAURO A W Combined effects of refrigerant leakages and fouling on air-source heat pump performances in cooling mode[J]. Applied Thermal Engineering, 2022, 204: 117965
doi: 10.1016/j.applthermaleng.2021.117965
|
20 |
KNABBEN F T, RONZONI A F, HERMES C J L Effect of the refrigerant charge, expansion restriction, and compressor speed interactions on the energy performance of household refrigerators[J]. International Journal of Refrigeration, 2021, 130: 347- 355
doi: 10.1016/j.ijrefrig.2021.06.006
|
21 |
金梧凤, 张宁宁, 张燕, 等 可燃制冷剂R32室内空调器泄漏扩散特性的实验研究[J]. 制冷学报, 2015, 36 (6): 10- 16 JIN Wu-feng, ZHANG Ning-ning, ZHANG Yan, et al Experimental study on leakage and diffusion characteristics of combustible refrigerant R32 indoor air conditioner[J]. Journal of Refrigeration, 2015, 36 (6): 10- 16
|
|
Viewed |
|
|
|
Full text
|
|
|
|
|
Abstract
|
|
|
|
|
Cited |
|
|
|
|
|
Shared |
|
|
|
|
|
Discussed |
|
|
|
|