Please wait a minute...
JOURNAL OF ZHEJIANG UNIVERSITY (ENGINEERING SCIENCE)
Electrical Engineering     
Adaptive resonance damping of LCL filtered grid connected inverter
ZHANG Ben ben,XU Fang,WU Le bin,AI Qing ling
College of Mechanical Engineering,Zhejiang University of Technology,Hangzhou 310014,China
Download:   PDF(1259KB) HTML
Export: BibTeX | EndNote (RIS)      

Abstract  

When grid is weak,inductance capacitor inductance (LCL) filtered inverter's resonance damped method by cascading notch filter in forward channel of current controller may be failed. A method was proposed to correct the notch frequency of notch filter by detecting the system resonance frequency on line in order to solve the problem.  Then a biquad filter was proposed instead of notch filter as the correct object. Then notch frequency and the proportion factor of PI controller were corrected. Experiments validate that the proposed method can efficiently improve the weak grid adaption of LCL filtered inverters.



Published: 31 March 2016
CLC:  TM 464  
Cite this article:

ZHANG Ben ben,XU Fang,WU Le bin,AI Qing ling. Adaptive resonance damping of LCL filtered grid connected inverter. JOURNAL OF ZHEJIANG UNIVERSITY (ENGINEERING SCIENCE), 2016, 50(1): 180-185.

URL:

http://www.zjujournals.com/eng/10.3785/j.issn.1008-973X.2016.01.026     OR     http://www.zjujournals.com/eng/Y2016/V50/I1/180


LCL型并网逆变器自适应谐振抑制

针对弱电网时在电流控制器前向通路串联陷波器的电感 电容 电感(LCL)型并网逆变器谐振抑制方法可能失效的问题,提出采用自适应陷波器的新方法.通过对基于陷波器的有源阻尼方法机理研究,得到该方法的实质是实现传递函数的零极点对消,提出采用在线检测系统谐振频率的方法实时修正陷波器的陷波频率.为了简化数字运算,将陷波器改进为可独立配置零极点的双二阶滤波器,根据所测系统的谐振频率修正PI控制器的比例系数,以保证系统的带宽及稳定性.实验证明,采用所提方案可以有效地提高LCL滤波并网逆变器的弱网适应性.

[1] BLAABJERG F, TEODORESCU R, LISERRE M, et al. Overview of control and grid synchronization for distributed power generation systems [J]. IEEE Transactions on Industrial Electronics, 2006, 53(5): 1398-1409.
[2] NISHIDA K, AHMED T, NAKAOKA M, et al. A novel finite time setting control algorithm designed for grid connected three phase inverter with LCL type filter [J]. IEEE Transaction on Industrial Applications, 2014, 50(3): 2005-2020.
[3] XU Jin ming, XIE Shao jun, TANG Ting. Active damping based control for grid connected LCL filtered inverter with injected grid current feedback only [J]. IEEE Transactions on Industrial Electronics, 2014, 61(9): 4746-4758.
[4] PENA ALZOLA R, LISERRE M, BLAABJERG F, et al. Analysis of the passive damping losses in LCL filter based grid converters [J]. IEEE Transactions on Power Electronics, 2013, 28(6): 2642-2646.
[5] 潘冬华, 阮新波, 王学华, 等. 提高LCL型并网逆变器鲁棒性的电容电流即时反馈有源阻尼方法[J]. 中国电机工程学报, 2013, 33(18): 1-10.
PAN Dong hua, RUAN Xin bo, WANG Xue hua, et al. A capacitor current real time feedback active damping method for improving robustness of the LCL type grid connected inverter [J]. Proceedings of the CSEE,2013,33(18):  1-10.
[6] DANNEHL J, FRIEDRICH F, STEFFAN H, et al. Investigation of active damping approaches for pi based current control of grid connected pulse width modulation converters with LCL filters [J]. IEEE Transactions on Industrial Applications, 2010, 46 (4): 1509-1517.
[7] HOUARI A, RENAUDINEAU B, MOBARAKEH N, et al. Large signal stability analysis and stabilization of converters connected to grid through LCL filters [J]. IEEE Transactions on Industrial Electronics, 2014, 61(12): 6507-6516.
[8] KOIWA K, ROSYADI M, UMEMURA A, et al. Sensorless virtual resistance damping method for grid connected three phase PWM converter with LCL filter [C]//2013 International Conference on Electrical Machines and Systems (ICEMS). Busan: IEEE, 2013: 1746-1749.
[9] DANNEHL J, FUCHS F, THOGERSEN P. PI State space current control of grid connected PWM converters with LCL filters [J]. IEEE Transactions on Power Electronics, 2010, 25(9): 2320-2330.
[10] KUKKOLA J, HINKKANEN M. Observer based state space current control for a three phase grid connected converter equipped with an LCL filter [J]. IEEE Transactions on Industry Applications, 2014, 50(4): 2700-2709.
[11] DANNEHL J, LISERRE M, FUCHS F. Filter based active damping of voltage source converters with LCL filter [J]. IEEE Transactions on Industrial Electronics, 2011, 58 (8): 3623-3633.
[12] 祝龙记, 张旭立. 光伏并网逆变器LCL陷波校正滤波器[J]. 电工技术学报, 2012, 27(9): 237-241.
ZHU Long ji, ZHANG Xu li. LCL filter with notch correct of grid connected photovoltaic inverters [J]. Transaction of CES, 2012, 27(9): 237-241.
[13] 许津铭, 谢少军, 唐婷. 弱网下LCL滤波并网逆变器自适应电流控制[J]. 中国电机工程学报, 2014, 34(24): 4031-4039.
XU Jin ming, XIE Shao jun, TANG Ting. An adaptive current control for grid connected LCL filtered inverters in weak grid case [J]. Proceedings of the CSEE, 2014, 34(24): 4031-4039.
[14] PENA ALZOLA R, LISERRE M, BLAABJERG F, et al. A self commissioning notch filter for active damping in a three phase LCL filter based grid tied converter [J]. IEEE Transactions on Power Electronics, 2014, 29(12): 6754-6761.
[15] LISERRE M, BLAABJERG F, TEODORESCU R. Grid impedance estimation via excitation of LCL filter resonance [J]. IEEE Transactions on Industry Applications, 2007, 43(5): 1401-1407.