考虑互联网数据中心灵活调度的柔性配电网运行优化方法
|
|
高本瑞,于仲安,陈锋升,王梓耀,潘振宁
|
Flexible distribution network operation optimization method incorporating flexible Internet data center scheduling
|
|
Benrui GAO,Zhongan YU,Fengsheng CHEN,Ziyao WANG,Zhenning PAN
|
|
| 表 4 改进的IEEE16节点鲁棒优化仿真结果对比 |
| Tab.4 Simulation results comparison of improved IEEE16 bus robust optimization |
|
案 例 | 工作 负载 | 只考虑配电网运行成本(w1=1) | | 只考虑IDC购电成本(w2=1) | | 考虑整体成本(w1=w2=0.5) | | Cvol/kV | Ccut/(kW·h) | Cidc/千元 | ΔUmax/% | | Cvol/kV | Ccut/(kW·h) | Cidc/千元 | ΔUmax/% | | Cvol/kV | Ccut/(kW·h) | Cidc/千元 | ΔUmax/% | | 1 | 1 | 218.77 | 19.14 | 26.84 | 0.96 | | 311.22 | 32 670.06 | 20.86 | 1.75 | | 239.11 | 17.10 | 21.29 | 1.15 | | 2 | 228.57 | 18.63 | 30.12 | 0.97 | | 322.80 | 32 670.06 | 24.06 | 2.22 | | 247.38 | 17.81 | 24.59 | 1.15 | | 2 | 1 | 218.90 | 34.93 | 26.85 | 0.55 | | 390.38 | 55 538.36 | 20.87 | 0.55 | | 238.83 | 33.54 | 21.45 | 0.55 | | 2 | 228.44 | 35.57 | 30.48 | 0.55 | | 398.66 | 55 293.06 | 24.07 | 0.55 | | 246.82 | 34.39 | 24.75 | 0.55 | | 3 | 1 | 233.77 | 33.03 | 29.22 | 0.54 | | 392.13 | 57 481.03 | 25.23 | 0.55 | | 244.38 | 31.74 | 26.17 | 0.54 | | 2 | 228.48 | 35.27 | 30.50 | 0.54 | | 397.42 | 55 410.85 | 24.19 | 0.55 | | 246.66 | 34.14 | 24.79 | 0.55 | | 4 | 1 | 109.68 | 9.79 | 29.59 | 0.54 | | 514.62 | 45 457.36 | 25.22 | 0.55 | | 120.38 | 9.28 | 25.71 | 0.54 | | 2 | 99.38 | 10.40 | 31.13 | 0.54 | | 532.81 | 46 155.27 | 24.18 | 0.55 | | 117.92 | 8.35 | 24.66 | 0.54 |
|
|
|