基于测量波阻抗的同杆双回输电线路故障识别
叶睿恺,吴浩,董星星

Fault identification of double-circuit transmission lines on same tower based on measuring wave impedance
Rui-kai YE,Hao WU,Xing-xing DONG
表 2 同杆双回线路外部故障时算法性能测试结果
Tab.2 Algorithm performance test results for external fault of double-circuit transmission line on same tower
序号 故障类型 l / km $\theta \,/\,( ^ \circ )$ ${R_{\rm{T}}}$ / Ω ${{{K}}_{\rm{s}}}\left| {{Z_{\rm{sM} }}} \right|\,/\,({10^3}\;\Omega )$ $\left| {{{{Z}}_{{\rm{dM}}}}} \right|\,/\,(1{0^{ - 9}}\;\Omega )$ ${{{K}}_{\rm{s}}}\left| {{{{Z}}_{{\rm{sN}}}}} \right|\,/\,({10^3}\;\Omega )$ $\left| {{{{Z}}_{{\rm{dN}}}}} \right|\,/\,(1{0^{ - 9}}\;\Omega )$ 判断结果
1 CG 50 15 200 8.992 12.464 4.402 0.109 区外故障
BCG 50 15 200 9.055 0.135 4.396 0.208
ABCG 50 15 200 8.994 0.122 4.396 0.168
2 CG 100 120 500 8.253 0.396 4.402 2.249 区外故障
BCG 100 120 500 8.257 0.360 4.402 0.126
ABCG 100 120 500 8.257 0.110 4.402 0.138
3 AG 50 8 100 8.978 6.865 4.402 0.253 区外故障
AG 50 15 100 8.995 2.353 4.402 0.260
AG 50 45 100 9.014 0.252 4.402 0.195
AG 50 90 100 9.038 1.256 4.402 0.183
AG 50 120 100 9.007 1.411 4.401 0.244
4 AC 100 8 8.184 2.354 4.402 0.152 区外故障
AC 100 15 8.208 4.916 4.402 0.259
AC 100 45 8.405 2.649 4.402 0.024
AC 100 90 8.407 0.430 4.402 0.023
AC 100 120 8.361 0.353 4.401 0.071
5 BG 50 45 0 9.050 1.126 4.406 0.069 区外故障
BG 50 45 100 9.045 3.267 4.406 0.423
BG 50 45 300 9.040 13.983 4.406 0.617
BG 50 45 600 9.037 12.736 4.406 5.109