表 1 同杆双回线路内部故障时算法性能测试结果
Tab.1 Algorithm performance test results for internal fault of double-circuit transmission line on same tower
序号 故障类型 l / km $\theta \,/\,(^ \circ )$ ${R_{\rm{T}}}$ / Ω ${K_{\rm{s} } }\left| { {Z_{\rm{sM} } } } \right|\,/\,({10^3}\;\Omega )$ $\left| { { { {Z} }_{ {\rm{dM} } } } } \right|\,/\,(1{0^4}\;\Omega )$ ${ { {K} }_{\rm{s} } }\left| { { { {Z} }_{ {\rm{sN} } } } } \right|\,/\,({10^3}\;\Omega )$ $\left| { { { {Z} }_{ {\rm{dN} } } } } \right|\,/\,(1{0^4}\;\Omega )$ 判断结果
1 ⅡBGG 100 90 200 1.156 1.089 1.223 1.078 区内故障
ⅠBCG 100 90 200 1.157 1.089 1.223 1.078
ⅠBCⅡAG 100 90 200 1.157 1.089 1.223 1.078
2 ⅡBGG 200 8 500 1.115 1.103 1.098 1.105 区内故障
ⅠBCG 200 8 500 1.115 1.103 1.097 1.105
ⅠBCⅡAG 200 8 500 1.115 1.103 1.097 1.105
3 ⅠAⅡBG 150 8 50 1.087 1.110 1.087 1.110 区内故障
ⅠAⅡBG 150 15 50 1.114 1.105 1.114 1.105
ⅠAⅡBG 150 45 50 1.087 1.110 1.087 1.110
ⅠAⅡBG 150 90 50 1.087 1.110 1.087 1.110
ⅠAⅡBG 150 120 50 1.159 1.088 1.159 1.088
4 ⅠABCⅡA 200 8 1.087 1.110 1.087 1.110 区内故障
ⅠABCⅡA 200 15 1.114 1.105 1.114 1.105
ⅠABCⅡA 200 45 1.087 1.110 1.087 1.110
ⅠABCⅡA 200 90 1.098 1.105 1.098 1.105
ⅠABCⅡA 200 120 1.098 1.105 1.098 1.105
5 ⅡACG 250 45 0 1.087 1.112 1.106 1.101 区内故障
ⅡACG 250 45 100 1.103 1.108 1.087 1.107
ⅡACG 250 45 300 1.105 1.107 1.085 1.108
ⅡACG 250 45 600 1.105 1.107 1.084 1.108