特高压直流输电线路差动保护改进方案
|
夏经德,罗金玉,高淑萍,焦作滨,邵文权,黄新波
|
Improved scheme for differential protection of UHVDC transmission lines
|
Jing-de XIA,Jin-yu LUO,shu-ping GAO,zai-bin JIAO,wen-quan SHAO,Xin-bo HUANG
|
|
表 1 区内故障时不同故障位置和过渡电阻的保护特性仿真结果 |
Tab.1 Test results of various internal faults occurring at different points with various resistances |
|
X/km | ${R_F}$/ $\Omega $ | $t'$/ms | ${I_{\rm op}}$/kA | ${I_{{\rm{res}}}}$/kA | 判据成立情况 | 0.01 | 0 | 0.7 | 0.350 | 0.001 | 成立 | 100 | 1.1 | 0.323 | 0.010 | 成立 | 300 | 1.8 | 0.353 | 0.007 | 成立 | 100 | 0 | 1.5 | 0.370 | 0.015 | 成立 | 100 | 1.8 | 0.343 | 0.012 | 成立 | 300 | 2.4 | 0.343 | 0.012 | 成立 | 400 | 0 | 2.7 | 0.399 | 0.001 | 成立 | 100 | 3.1 | 0.340 | 0.002 | 成立 | 300 | 5.3 | 0.749 | 0.417 | 成立 | 700 | 0 | 4.8 | 1.150 | 0.819 | 成立 | 100 | 5.0 | 0.811 | 0.458 | 成立 | 300 | 5.3 | 0.569 | 0.218 | 成立 | 1 000 | 0 | 3.7 | 0.826 | 0.428 | 成立 | 100 | 3.9 | 0.587 | 0.210 | 成立 | 300 | 4.2 | 0.397 | 0.073 | 成立 | 1 400 | 0 | 1.3 | 1.623 | 1.307 | 成立 | 100 | 2.3 | 1.332 | 1.013 | 成立 | 300 | 3.5 | 0.884 | 0.562 | 成立 | 1 417.99 | 0 | 2.2 | 1.614 | 1.260 | 成立 | 100 | 2.9 | 1.126 | 0.799 | 成立 | 300 | 4.0 | 0.750 | 0.435 | 成立 |
|
|
|