Electrical & Electronic Engineering |
|
|
|
|
Mixed nonlinear dynamic voltage phasor tracing method based on WAMS/SCADA |
Xiao-gang CHEN, Yong-hui YI, Wei WANG, Quan-yuan JIANG, Chuang-xin GUO, Yi-jia CAO |
School of Electrical Engineering, Zhejiang University, Hangzhou 310027, China; Hangzhou Electric Power Bureau, Hangzhou 310009, China; Zhejiang Provincial Electric Power Company, Hangzhou 310007, China |
|
|
Abstract By considering the static voltage characteristic of the load, we propose a WAMS/SCADA mixed nonlinear method to estimate the voltage of unobservable buses caused by topology change or phasor measurement unit (PMU) malfunction in a power system. By modeling the load characteristic with data from SCADA, we employed the Gauss-Seidel method to solve the nonlinear equations and estimate the voltage of unobservable buses with the high precision voltages of neighboring buses measured by a PMU. Simulations were carried out on the IEEE 39-bus system, and the results show that this novel method can dynamically and accurately trace the variation of the voltage phasor of the unobservable buses.
|
Received: 04 March 2008
Published: 02 May 2009
|
|
|
Viewed |
|
|
|
Full text
|
|
|
|
|
Abstract
|
|
|
|
|
Cited |
|
|
|
|
|
Shared |
|
|
|
|
|
Discussed |
|
|
|
|